- Brand: New Electric Power
- Capacity: Up to 18MVA
- Voltage: 6/10/11/15/20/22/33/35/69KV
- Connection group label:Customization
- Impedance voltage:Cutomization
- Standard:IEC/IEEE/ANSI
- Category: Oil Type Distribution Transformer
Principles for Selecting Transformers
1. The transformer capacity should be selected based on the calculated load, and the long-term load rate of the transformer should not exceed 85%.
2. The Distribution Transformer in the power supply and distribution system should be selected from the Dyn11 connection group.
3. The number of transformers should be selected based on load characteristics and economic operation. When one of the following conditions is met, it is advisable to install two or more transformers:
1) There is a large number of primary or secondary loads;
2) Seasonal load changes are significant;
3) Concentrated load is relatively large.
4. For substations equipped with two or more transformers, when either transformer is disconnected, the capacity of the remaining transformers should meet the electricity consumption of the first and second-level loads.
5. For loads with significant daily or seasonal fluctuations, power transformers with inconsistent capacity can be used after technical and economic comparison.
6. 20KV, 10KV, and 6kV distribution transformers should not be used on load voltage regulating transformers. Still, when the voltage deviation of the 20, 10, and 6kV power supply cannot meet the requirements, and the user has equipment with strict voltage requirements. It is not reasonable to set up a separate voltage-regulating device technology; 20, 10, and 6kV on-load voltage regulating transformers can also be used. In distribution areas with large voltage fluctuations and the need for frequent voltage regulation, it is recommended to use an on-load voltage-regulating transformer.
Tongrun Photoelectron is a comprehensive enterprise integrating product research and development, product sales, and import and export services. It has more than 45 years of research and development experience. The company has a modern workshop of more than 120,000 square meters, a research and development center, and a staff apartment of more than 30,000 square meters. The production equipment is perfect, the testing method is perfect, the technical force is strong, and the qualification is complete. We can provide high, medium, and Low Voltage Transformers with voltages of up to 110KV and capacities of up to 120,000 kVA for various purposes, as well as Tap Changer, Gas Relay, oil level gauge, Moisture Absorber, Pressure Relief Valve, Butterfly Valve, thermometer, insulation terminal, cross flow fan, Transformer bushing, and other accessories.
Brand: PDDN
Place Of Origin: China
Use: Power, Electronic, Lighting, Audio, Potential, Instrument, Rectifier, Pulse, Reactor
Phase: Three
Coil Structure: Toroidal
Number Of Coils: Autotransformer
Product Name: Oil immersed distribution transformer
Rated Capacity: 30kva~2500kva
Rated Primary Voltage: 6kv/10kv/11kv/13.8kv//15kv/20kv/22kv/33kv/35kv/
Rated Secondary Voltage: 380v/400v/415v/420v
Rated Power: 20kw~2000kw
Frequency: 50Hz/60Hz
Insulation Class: A
Cooling Mode: ONAN
Connection Group Number: Dyn11/Dyn0
Core Material: Copper / aluminum